ClearTank Buggy 70 Mobile Fuel Cleaning Buggy

Mobile fuel cleaning buggies protect generators and equipment that operates in contaminated areas. Standby gensets have a low workload. Their day tanks can store fuel for months or even years. Such conditions encourage fuel contamination and threaten the reliability of the genset. The ClearTank Buggy 70 is an economical way to tackle contamination in storage tanks up to 10,000 litres. It can be wheeled between locations, keeping smaller fuel stores clean and dry.

The ClearTank Buggy 70 is a self-contained unit that only needs a connection to a mains power supply. Its simple control panel can be operated by general maintenance staff and does not require specialist knowledge or lengthy training.

Key advantages of the ClearTank Buggy 70

 

Features of the ClearTank Buggy 70

Standard Features:

  • Water bypass that enables you to remove bulk water from your tanks without overloading the filters.
  • 7″ bag filter for bulk filtration of dirty fuel.
  • Water absorption filtration (with bypass connection).
  • Design for unattended operation:
    • Bund flooded shut off.
    • Filter blocked shut off.
    • Timed on/off 7-day cycles.
  • Dry break QRC couplings.
  • Inline flow meter.

Optional Features:

  • Particle counter:
    • Instant readout of particle counts.
    • Cleanliness codes displayed in NAS 1638, ISO 4406 and SAE A5 4059.
    • Trending software to log and display fuel cleanliness over time.

 

Specifications of the ClearTank Buggy 70

Power
Voltage 110, 230
Frequency 50Hz
Maximum variations Voltage: +/- 5% of the nominal value Frequency: +/-2% of the nominal value
Nominal wattage 1kW
Pump
Motor protection Thermal overload protection
Flow rate 70 litres per minute
Suction lift 2.5 metres
System pressure Up to 2 bar
Filtration
Particulate 1, 5, 20 micron filters available
Water Dual element water absorption
Environmental & Physical
Noise Under normal working conditions the noise level does not exceed 70dB(A) at a distance of 1 meter from the electric pump.
Weight 165 kg
Dimensions H:1,180mm, W:780mm, D:670mm
Pipework 1″ pipework with 1″ ISO B QRC inlet and outlet ports
Permitted Use
Diesel fuel viscosity 2 to 5.35 centistokes @ 37.8°C
Minimum flash point (Pensky-Martens) 55°C

 

“High-Ambient” Model
Power supply Single Phase 220V
Frequency 60Hz
All other features are the same as the standard model.